Vlf Cable Test Set
The vlf test instrument should be solidly grounded before connecting up any cables.
Vlf cable test set. Hva200 high voltage test set new hva systems detect faults in cable networks in a non destructive yet efficient way and fulfill all the requirements of modern cable. The vlf cable testing time varies from 15 to 60 minutes. There are no rules of thumb to be used. When comparing this figure to power frequency ac or 0 1 hz vlf cos rectangular the tree growth rate is only 2 2 5 9 and 3 4 7 8 mm h.
Very low frequency is the preferred method over 60hz for two reasons. Ground cable figure 4. Vlf cable test voltages and time durations are set by ieee standard 400 2 2013. The hva28td vlf high voltage test set is an ultra compact lightweight 0 1 hz vlf cable tester with integrated tan delta diagnostics.
Hva68 2 cable tester new hva90 insulation tester. Critically the test object still receives the alternating sinusoidal voltage that would be supplied through everyday use but the size of the test equipment is. Subsequent work by the cdfi has shown there to be no significant change in the efficacy of a vlf test conducted over the frequency range 0 1 to 0 01 hz when the ieee 400 2 voltages and times are used. Connection setup for a vlf cable connecting a vlf test instrument to a cable refer to ieee 400 2 for safety guidelines.
Ieee 400 2 establishes some suggested test voltages and times. A very low frequency vlf withstand test is an ac withstand test usually carried out at a frequency between 0 1 hz and 0 01 hz. At a typical vlf frequency of 0 1hz it takes 600 times less power to test the same cable compared to 60 hz. Hva28 td vlf test set at a glance.
With monitored withstand test mwt testing and diagnostics in compliance with ieee400. The increased load capability in field applications in which 60 hertz is too bulky and expensive making it nearly impossible to test a cable of considerable length. Hva40 5 hipot tester new hva45td vlf high voltage test set new hva60 ac hipot. A typical 15 kv medium voltage cable in usa has an insulation thickness of 0 22 5 6 mm and therefore during a vlf test time of 30 minutes all defects within the cable should grow to failure.
Because vlf testing supplies a working frequency of 0 1hz as opposed to the 50 60hz usually required for live transmission the physical size of the vlf test set is massively reduced.